Product Overview:
OT603R Addressable Heat (Thermal) Detector is designed to meet the stringent performance requirements of industrial and municipal fire detection/alarm systems.
With a precise NTC resistor which can sense the environment temperature. The detector initiates an alarm in response to both rapid rate-of-rise condition (increases in excess of 6.7°C per minute) and fixed temperature.
It has automatic compensation for excursion and complete self-diagnosis that can greatly reduce false alarm.
SEND INQUIRY NOWCharacteristics And Benefits:
Built-in microprocessor and intelligent software, ensuring the utmost accuracy with controller.
2 bus lines current PWM digital transmission technology with great reliability
Special methods for dampproof , antisepsis and mildew proof.
SMT technology, firmly, high secure and anti-jamming.
Easy plug-in of the head to base
SEMS screws for easy wiring
2-wire without polarity
Comply with Standard: GB4716-2005
Specifications
Operating Voltage | DC20V~DC30V |
Standby Current | ≤0.4 mA Alarm current: ≤2 mA |
Wiring | Non-polarized 2 bus lines Alarm threshold: 57°C or 6.7°C/minute |
Operating Environment | Temperature: -10°C ~50°C Related Humidity: ≤95% (40±2°C) |
Dimensions | Diameter 100 mm Height 41 mm Weight: 65g |
To meet various requirements in your market, we pride to offer complete fire protection system and standalone products. For OEM/ODM service, please go to OEM/ODM