The FW2841 Conventional Zone Module is an intelligent, addressable device designed to operate with a Maple Armor fire alarm control panel. It requires one address on the signaling line circuit (SLC).
This module interfaces and monitors 2-wire conventional detectors in Class B wiring. The initiating zone can support a mix of 2-wire conventional automatic detectors and normally open dry contact alarm initiating devices such as mechanical heat detectors and manual stations.
It is a UL-listed device, according to UL864 and ULC-S527, for in door use in fire protective signaling systems.
Specifications
Nominal Voltage: 24 VDC
Operating Voltage Range: 13 to 28 VDC
Standby Current: ≤0.8 mA
Active Current: ≤1.7 mA
External Input PowerSupply: 18.5 VDC to 28 VDC compatibility range
Max. Line Impedance: 25 Ω for Input Circuit, 6.6KΩ for Grounding
Max. Rated Operating Voltage Range: 15.5 V – 27.5 V
Max. Alarm Current: 43 mA
Max. Capacitance Loading: 1 uF
Min. Normal Standby Impedance: 5.5 KΩ
Max. Alarm Reset Voltage: 0.2 V
Min. Alarm Reset Time: 9 s
Max. Alarm Verification Retard Reset Time: 40 s
Max. Detector Restart Time for Alarm Verification: 40 s
Compatible EOLR: 2 KΩ to 5.6 KΩ
Operating Temperature: -10° C to 55° C (14° F to 131° F)
Operating Humidity: 0 to 95% RH Non-condensing
Installation Environment: Dry indoor use only
Housing Material: High impact plastic
Dimension: 120 mm (L) x 120 mm (W) x 45 mm (H)
Wire Connections: Screw terminal
Wire Size: 18 to 12 AWG (0.82 mm2 to 3.31 mm2)
Compatible Bases: FW800 Surface Mount Box, FW801 Deep Surface Mount Box
•Compatible FACP: FW2105, FW2107
Regulatory Compliance: UL/ULC, FCC, CSFM
Features
• Durable material and solid parts
• Visible status LED indicators for alarm and trouble
• Easy installation
• Supports Class A and Class B inputs
• Mounts to a standard 4-inch square electrical box
• For dry indoor installation
• Up to 252 addressable devices per loop
• Address programmed via handheld programmer
Installation
The FW2841 Conventional Zone Module can be flush mounted to standard North American 4-inch square boxes. A Maple Armor plastic surface box is alsoavailable.

Wiring
Field wiring is to be completed using the module's screw terminals. The terminals are suited for 18 to 12 AWG (0.82 mm2 to 3.31 mm2) wire size.

Ordering Information