The FW2821 Supervised Output Module is an intelligent, addressable device designed to operate with a MapleArmor fire alarm control panel. It requires one address on the signaling line circuit (SLC).
It is used to connect a single 24VDC output and a single Alarm, Supervisory, Trouble, or Monitor-type dry contact Initiating Device Circuit (IDC). The module's programming options in the panel determine this.
This module supports a single Class B, normally open or normally closed. It connects to a dry contact initiating device circuit (IDC) and must terminate with an EOL.
According to UL864 and ULC-S527, it is a UL-listed device for indoor use in fire protective signaling systems.
Specifications
Nominal Voltage: 24 VDC
Operating Voltage Range: 13 to 28 VDC
Standby Current: ≤0.2mA
Alarm Current: ≤0.35mA
External Input Power Supply: 24VDC (nominal)15.4VDC to 26.4VDC compatible range
Active Current (Output): 2A, 0.35pF
Output Range: 15.1 to 26.4 VDC
Max. Line Impedance: 25 Ω for Input Circuit, 1 Ω for Output Circuit
Recommended Test Impedance: 5 MΩ for Open Circuit trouble, 0.1 Ω for Short Circuit trouble
Max. Impedance for Grounding: 6.6 KΩ
Compatible EOLR: 10KΩ
Operating Temperature: -10° C to 55° C (14° F to 131° F)
Operating Humidity: 0 to 95% RH Non-condensing
Installation Environment: Dry indoor use only
Housing Material: High impact plastic
Dimension: 120 mm (L) x 120 mm (W) x 45 mm (H)
Wire Connections: Screw terminal
Wire Size: 18 to 12 AWG (0.82 mm2 to 3.31 mm2)
Compatible Bases: FW800 Surface Mount Box, FW801 Deep Surface Mount Box
•Compatible FACP: FW2105, FW2107
Regulatory Compliance: UL/ULC, FCC, CSFM
Features
• Durable material and solid parts
• Two visible status LED indicators for alarm and trouble
• Easy installation
• Supports one Class B input and one Class B output
• Input latched/non-latched selectable
• Mounts to a standard 4-inch square electrical box
• For dry indoor installation
• Up to 252 addressable devices per loop
• Address programmed via handheld programmer
Installation
The FW2821 Supervised Output Module can be flush mounted to standard North American 4-inch square boxes. A Maple Armor plastic surface box is alsoavailable.

Wiring
Field wiring is to be completed using the screw terminals on the module. The terminals are suited for 18 to 12 AWG (0.82 mm2 to 3.31 mm2) wire size.