  1. 1. Overview

  2. The FW2105 is a modular addressable fire alarm control panel designed to meet the requirements of a wide range of small to medium size fire alarm systems and fits standalone application and multi-panel networks. It features a digital signal processor-based design, fully configurable from the front panel with password protection. The standard FW2105 control panel supports one Signaling Line Circuit (SLC) and 4 Notification Appliance Circuits (NACs). It is equipped with 4 form C dry relay contacts dedicated to Fire Department connections and has 10 amps of power. It supports up to 9 Addressable Signaling Line Circuits (SLCs), accommodating up to 252 addressable devices or points per SLC, up to 12 Notification Appliance Circuits (NACs), and 4 onboard Form C dry contact relays. The FW2105 is compatible with the Series 2 Maple Armor devices, and it meets the requirements of UL 864, and CAN/ULC-S527.


FW2105 is networkable with up to 99 panels in Class B or 31 in Class A, and features a 7-inch, 8-line LCD display, 40 onboard LED zone indicators, and robust event storage (4,000 alarms, 12,000 other events). Additional highlights include battery support (hosts 2x 18Ah in case, charges up to 55Ah), multiple wiring knockouts, proper ventilation, and flexible mounting options.


2. Features

• 8-line colored 7”LCD with 800 X 480 resolution 

• 12 LED indicators, making it a highly intuitive fire alarm interface with 6 auxiliary function keys 

• Up to 9 signaling line circuits (SLC), Class A or Class B. each supports 252 intelligent devices 

• Supports FW Series intelligent detectors, manual stations, and modules 

• Up to 12 notification appliance circuits (NAC), Class A or Class B 

• Automatic addressing function allowing the panel to sequentially assign addresses 

• Programmable via PC configuration software or Field programmable through front panel. 

• Modular design for custom system configurations. 

• USB port on board for programming and firmware upgrade. 

• Supports remote annunciators' network for wide system configurations and applications. 

• Form C dry relay contacts dedicated for Alarm, Trouble, Supervisory, and Monitor. 

• Supports positive alarm sequence to avoid false alarms 

• Configurable for Two Stage operation 

• Supports RJ45 and RS232 interface for third-party monitoring software 

• Four-levels of password protection with field- programmable definitions enable the installer to determine which functions are accessible at each password level 

• Two separate event history logs. Includes a 1000 alarm event Log and 5000 non alarm event log.

• Optional DACT (Digital Alarm Communicator Transmitter) contains two switched public telephone network circuits, One DACT supportstransmitting the status of software zones, System Trouble, and Supervisory. Admeco Contact ID, SIA Format, And Standalone Radio/Cell Units.

• Optional Conventional Zone Unit features 8 Initiating Device Circuits (IDC) that connectconventional zones to the control panel. This card provides the perfect solution for conventional retrofit applications.


3. Specifications:

Primary Supply: 110 - 120 VAC 60Hz, 5.5A max. / 220 - 240 VAC 50Hz, 3.1 A max 

Backup Battery: Voltage: 24 VDC, Two 12VDC in series; Type: Sealed lead acid; Charging capacity: 55AH; Charging current: 2.8 A max; Up to two 18 Ah batteries can fit in the control panel enclosure. 

Auxiliary Power Source: Two Power Limited Outputs, Output range: 20.4 ~27.4 VDC, Output current: 510mA in total (normal standby), 1.0A in total (alarm), Non-Resettable/Resettable Power Output (configurable)  

SLC (Signaling Loop Circuit): 1 loop, expandable to 9 loops, Class A and Class B, each loop supporting up to 252 addressable devices, Maximum normal standby current per MFU/ALU: 100mAMaximum alarm current per MFU/ALU: 300mA 

NACs (Notification Appliance Circuits): Up to 12 Class A/DCLA and Class B/DCLB circuits, 3.0 A each max per circuit, total 10 A max in the panel, 1.0 A max regulated 24VDC output. 

Annunciator Network Circuits: Up to 4 ANC Class A/DCLA and Class B/DCLB circuits, 2 Wire Operation for both power and communication, Output voltage range: 19.4 - 24.3 VDC, Maximum load current: 320 mA

Relays Output: Four form C relays: Alarm, Supervisory, Trouble, and one programmable, Contact Rating: 2A @30VDC 

Recommended Testing Impendence: 6.6kΩ for ground fault, 10MΩ for open circuit, 0.1Ω for short circuit. 

Environmental: Operating temperature: 14 - 131°F (-10 - 55°C), Relative humidity: 0 to 95% at 90°F (32°C), non-condensing, To be installed in normal dry indoor environment only. 

Dimensions: 620×368×156mm (length×width×depth) 

Weight: 18KGS

Cable: 16AWG/1.5mm² or above shield or twisted fire-retardant cable


4. System Diagram


Basic Information
  • Year Established
    --
  • Business Type
    --
  • Country / Region
    --
  • Main Industry
    --
  • Main Products
    --
  • Enterprise Legal Person
    --
  • Total Employees
    --
  • Annual Output Value
    --
  • Export Market
    --
  • Cooperated Customers
    --

Get in touch with us

Just leave your email or phone number in the contact form so we can send you a free quote for our wide range of designs!

Recommended

They are all manufactured according to the strictest international standards. Our products have received favor from both domestic and foreign markets.
They are now widely exporting to 200 countries.

Send your inquiry

Choose a different language
╳
English
العربية
Deutsch
Tiếng Việt
Pilipino
ภาษาไทย
bahasa Indonesia
हिन्दी
русский
Português
italiano
français
Español
Current language:English