Earlier Alarm, Faster Fire-fighting, Less Loss.

Language
PRODUCTS
VR

Features:

◆  The high-sensitivity sensor is used to monitor the changes of VOC gas, smoke, temperature and CO gas in the environment in real time, and accurately predict the fire hazard and the early situation of the fire.

◆  3-level alarm strategy, intelligent judgment and analysis, to prevent false alarms and false negatives.

◆  System self-diagnosis, sensor fault or fire extinguisher line open circuit fault signal indication and output.

◆  Strong adaptability to high and low temperature environments

◆  Using CAN bus connection, it can communicate directly with BMS, and the wiring is convenient, and up to 10 detectors can be flexibly connected.

◆  Simple design, ultra-thin shape, height is only 22mm.


Specifications:

No.ItemsTechnical Indicators
1Operating VoltageDC9V36V
2Rated Power1.2W
3Environment Temperature-40+85
4Environment Humidity95%
5Electrostatic Discharge ESD 1.5KV
6Electrical Fast Transient/ Burst EFT level 4
7Communication ModeCAN
8Smoke Sensitivity Threshold0.25dB/m0.45dB/m
9Temperature Alarm Threshold (Level 1)6270
10Temperature Activate Threshold (Level 2)8590
11Battery Fluid Leakage Alarm Threshold (VOC)≥55mg/m3 / ≥200ppm
12CO Alarm Threshold300ppm+/-50ppm
13Monitoring Area0.6m3 confined space
14Enclosure MateriaAlumina
15Dimensions87mm (L) × 56mm (W) × 22mm (H)
16Weight60g


Wiring:


Feature Descriptions:

The detector has smoke, temperature, carbon monoxide and battery leakage VOC gas detection and alarm functions, and the detector has 3 levels of alarm strategy:

Level 1 Alarm Strategy: (Note: Level 1 alarm is not associated with fire extinguishing output)

1. The detector detected smoke above the threshold (≥0.25dB/m);

2. The detector detected that the carbon monoxide gas concentration had reached a threshold (≥190ppm+/-50ppm);

3. The detector detected that both temperature sensors detected temperatures greater than 62 degrees Celsius;

4. The detector detected that the concentration of volatile gases (VOCs) reached above the threshold (≥55mg/m3 or 200ppm)

Level 2 Alarm Strategy: The level 2 alarm strategy refers to the corresponding measures when any 2 alarms in items 1~4 of the level 1 alarm strategy are addressed. During the alarm level 2, the extinguishing output can be manually controlled by operating the rocker switch connected to the detector.

Level 3 Alarm Strategy: The 3-level alarm strategy refers to the alarm sent by the detector when the temperature above 85 degrees is detected by both temperature sensors inside the detector. When a level 3 alarm occurs, the detector will automatically output a fire extinguishing signal and turn on the fire extinguisher for fire suppression.

 

Fire extinguishing output and fire extinguishing feedback:

Manual extinguishing output: When a level 2 alarm occurs, manual fire extinguishing control can be carried out by operating the rocker switch connected to the detector, the specific method is: press and hold the rocker switch button and hold for about 3~4 seconds, you can achieve manual fire extinguishing output.

Automatic fire extinguishing output: In the event of a Level 3 alarm, the detector automatically activates the extinguishing control output after a delay of 10 seconds.

Fire extinguishing feedback signal: After the fire extinguisher is successfully started, a set of passive contacts is output, and the detector automatically reports the fire extinguishing feedback signal after receiving the signal.






Basic Information
  • Year Established
    --
  • Business Type
    --
  • Country / Region
    --
  • Main Industry
    --
  • Main Products
    --
  • Enterprise Legal Person
    --
  • Total Employees
    --
  • Annual Output Value
    --
  • Export Market
    --
  • Cooperated Customers
    --

Get in touch with us

Just leave your email or phone number in the contact form so we can send you a free quote for our wide range of designs!

Recommended

They are all manufactured according to the strictest international standards. Our products have received favor from both domestic and foreign markets.
They are now widely exporting to 200 countries.

Send your inquiry

Choose a different language
English
العربية
Deutsch
Tiếng Việt
Pilipino
ภาษาไทย
bahasa Indonesia
हिन्दी
русский
Português
italiano
français
Español
Current language:English